Sunday, May 3, 2020

Power Factor free essay sample

Power factor: The power factor of an AC electric power system is defined as the ratio of the real power flowing to the load to the apparent power, and is a dimensionless number between O and 1 (frequently expressed as a percentage, e. g. 0. 5 pf= 50% pf). Real power is the capacity of the circuit for performing work in a particular time. Apparent power is the product of the current and voltage of the circuit. Due to energy stored in the load and returned to the source, or due to a non-linear load that distorts the wave shape of the current drawn from the source, the apparent power will be greater han the real power. In an electric power system, a load with low power factor draws more current than a load with a high power factor for the same amount of useful power transferred. The higher currents increase the energy lost in the distribution system, and require larger wires and other equipment. Because of the costs of larger equipment and wasted energy, electrical utilities will usually charge a higher cost to industrial or commercial costumers where there is a low power factor Linear loads with low power factor (such as induction motors) can be corrected with a passive network of capacitors or inductors. Non-linear loads, such as rectifiers, distort the current drawn from the system. In such cases, active or passive power factor correction may be used to counteract the distortion and raise the power factor. The devices for correction of the power factor may be at a central substation, spread out over a distribution system, or built into power-consuming equipment. Contents 1 Power factor in linear circuits 0 1. 1 Definition and calculation 0 1. 2 Power factor correction of linear loads 2 Non-linear loads 0 2. 1 Non-sinusoidal components 0 2. Switched-mode power supplies 0 2. Power factor correction in non-linear loads 2. 3. 1 passive PFC 2. 3. 2 Active PFC 3 Importance of power factor in distribution systems factor 5 Mnemonics 6 References 7 External links Power factor in linear circuits 4 Measuring power In a purely resistive AC circuit, voltage and current waveforms are in step (or in phase), changing polarity at the same instant in each cycle. All the power entering inductors, ener gy storage in the loads result in a time difference between the current and voltage waveforms. During each cycle of the AC voltage, extra energy, in addition o any energy consumed in the load, is temporarily stored in the load in electric or magnetic fields, and then returned to the power grid a fraction of a second later in the cycle. The ebb and flow of this nonproductive power increases the current in the line. Thus, a circuit with a low power factor will use higher currents to transfer a given quantity of real power than a circuit with a high power factor. A linear load does not change the shape of the waveform of the current, but may change the relative timing (phase) between voltage and current. Circuits containing purely esistive heating elements (filament lamps, strip heaters, cooking stoves, etc. ) have a power factor of 1. 0. Circuits containing inductive or capacitive elements (electric motors, solenoid valves, lamp ballasts, and others) often have a power factor below Definition and calculation AC power flow has the three components: real power (Active power) (P), measured in watts (W); apparent power (S), measured in volt-amperes (VA); and reactive power (Q), measured in reactive volt-amperes (var). The power factor is defined as: [pic] In the case of a perfectly sinusoidal waveform, P, Q and S can be expressed as ectors that form a vector triangle such that: [pic] If cp is the phase angle between the current and voltage, then the power factor is equal to the cosine of the angle, [pic], and: [pic] Since the units are consistent, the power factor is by definition a dimensionless number between O and 1 . When power factor is equal to O, the energy flow is entirely reactive, and stored energy in the load returns to the source on each cycle. When the power factor is 1, all the energy supplied by the source is consumed by the load. Power factors are usually stated as leading or lagging to show the ign of the phase angle. If a purely resistive load is connected toa power supply, current and voltage will change polarity in step, the power factor will be unity (1), and the electrical energy flows in a single direction across the network in each cycle. Inductive loads such as transformers and motors (any type of wound coil) consume reactive power with current waveform lagging the voltage. Capacitive loads such as capacitor banks or buried cable generate reactive power with current phase leading the voltage. Both types of loads will absorb energy during part of the AC cycle, which s stored in the devices magnetic or electric field, only to return this energy back to the source during the rest of the cycle. For example, to get 1 kW of real power, if the power factor is unity, 1 kVAof apparent power needs to be transferred (1 kW 1 † 1 kVA). At low values of power factor, more apparent power needs to be transferred to get the same real power. To get 1 kW of real power at 0. 2 power factor, 5 WA of apparent power needs to be transferred (1 kW + 0. 2 = 5 kVA). This apparent power must be produced and transmitted to the load in the conventional fashion, and is ubject to the usual distributed losses in the production and transmission processes. Electrical loads consuming alternating current power consume both real power and reactive power. The vector sum of real and reactive power is the apparent power. The power, and so, the electric load has a power factor of less than 1 . Power factor correction of linear loads It is often desirable to adjust the power factor of a system to near 1. 0. This power factor correction (PFC) is achieved by switching in or out banks of inductors or capacitors. For example the inductive effect of motor loads may be offset by locally onnected capacitors. When reactive elements supply or absorb reactive power near the load, the apparent power is reduced. Power factor correction may be applied by an electrical power transmission utility to improve the stability and efficiency of the transmission network. Correction equipment may be installed by individual electrical customers to reduce the costs charged to them by their electricity supplier. A high power factor is generally desirable in a transmission system to reduce transmission losses and improve voltage regulation at the load. Power factor correction brings the ower factor of an AC power circuit closer to 1 by supplying reactive power of opposite sign, adding capacitors or inductors which act to cancel the inductive or capacitive effects of the load, respectively.

No comments:

Post a Comment

Note: Only a member of this blog may post a comment.